The Allen-Bradley ControlLogix® system is a modular system that requires a 1756-A10/C ControlLogix chassis. The chassis are designed for only horizontal back-panel mounting. Place any module into any slot. The backplane provides a high-speed communication path between modules.

ControlLogix Rack 1756-A10/C Technical Specifications

Backplane current, chassis/slot max @ 1.2V DC 1.5 A/–
Backplane current, chassis/slot max @ 3.3V DC 4 A/4 A
Backplane current, chassis/slot max @ 5.1V DC 15 A/6 A
Backplane current, chassis/slot max @ 24V DC 2.8 A/2.8 A
Power dissipation Max. 5 W
Slots 10
Mounting method Only horizontal
Location Panel
Wire size
  • Functional earth ground - 8.3 mm² (8 AWG) solid or stranded copper wire rated at 90 °C (194 °F) or greater
  • Protective earth ground - 2.1 mm² (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F) or greater
North American temperature code T4
IEC temperature code T4
Enclosure type rating None (open-style)
Cabinet size (HxWxD) 50.8 x 76.2 x 20.3 cm (20 x 30 x 8 in.)
Weight Approx. 1.45 kg (3.2 lb)
Environmental  
Temperature, operating -25…+60 °C (-13…+140 °F)
Temperature, surrounding air
  • IEC 60068-2-1 (Test Ad, Operating Cold)
  • IEC 60068-2-2 (Test Bd, Operating Dry Heat)
  • IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
60 °C (140 °F)
Temperature, nonoperating
  • IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
  • IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
  • IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C (-40…+185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g
Emissions IEC 61000-6-4
ESD immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3
  • 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
  • 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
  • 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
  • 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Certifications  
c-UL-us
  • UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
  • UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CSA
  • CSA Certified Process Control Equipment. See CSA File 54689.
  • CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File 69960.
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations.
CE European Union 2004/108/EC EMC Directive, compliant with:
  • EN 61326-1; Meas./Control/Lab., Industrial Requirements
  • EN 61000-6-2; Industrial Immunity
  • EN 61000-6-4; Industrial Emissions
  • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM Australian Radiocommunications Act, compliant with:
EN 61000-6-4; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with:
  • EN 60079-15; Potentially Explosive Atmospheres, Protection “n”
  • EN 60079-0; General Requirements
  • II 3 G Ex nA IIC T4 Gc
  • DEMKO13ATEX1325026X
IECEx IECEx System, compliant with:
  • IEC 60079-15; Potentially Explosive Atmospheres, Protection ”n”
  • IEC 60079-0; General Requirements
  • II 3 G Ex nA IIC T4 Gc
  • IECExUL14.0008X
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
EAC
  • Russian Customs Union TR CU 020/2011 EMC Technical Regulation
  • Russian Customs Union TR CU 004/2011 LV Technical Regulation

Package includes:

  • 1x 1756-A10 Ser C ControlLogix 10-Slot Rack
  • 1x 1756-PB75 Ser B DC Power Supply
  • 1x 1756-L81E Ser B 3MB Controller
  • 1x 1756-ENBT Ser A Ethernet/IP Communications Module
  • 1x 1756-EN2TR Ser C 2-Port CLX Hi-Cap Enet/Ip Module
  • 1x 1756-IB32 Ser B D/I Module
  • 1x 1756-OB32 Ser A D/O Module
  • 2x 1756-IF4FXOF2F Ser B 6 Point Analog Combination Module